1.Overview:
The vertical high voltage electric motor belongs to the YL series. In simple terms, it is to supply power to machines that need to be installed vertically and drive large loads. There is no need to add additional transmission parts; it can be directly connected to the main shaft of the equipment. Compared with horizontal motors, its vertical structure allows direct integration with heavy machinery that requires vertical installation and vertical load transmission. This integration cuts out the need for extra transmission components like couplings or reducers, thus avoiding power losses caused by intermediate links and reducing unnecessary space occupation in the equipment layout.
Here are some additional data points:
|
Voltage |
3kV/6kV/10kV |
|
Power ratings |
200-2500kw |
|
Frame sizes |
355-630mm |
|
Protection ratings |
IP54 |
|
Duty |
S1 |
|
Cooling Method |
IC86W |
2.Core Features
The vertical structure offers high adaptability. This vertical high voltage electric motor features an integrated vertical design, with the motor shaft outputting directly upward or downward. This allows direct connection to the spindle of vertical equipment-such as vertical water pumps or vertical rolling mills-eliminating the need for additional gearboxes, couplings, or other directional or transmission components. Compared to the "horizontal motor + transmission bracket" combination, it reduces footprint by 30%-40%, making it particularly suitable for workshops with ample vertical space but limited horizontal space.
High-voltage heavy-load performance remains stable. The stator winding adopts vacuum pressure impregnation (VPI) technology, which achieves high insulation density and can withstand long-term exposure to 6kV/10kV high-voltage power grid surges. The rotor is made of laminated high-strength silicon steel sheets, which can maintain the operating vibration level below 0.08mm even at high power outputs of 200kW to 6000kW. This design prevents "shaft swing" during the vertical transmission process, ensuring stable operation of the equipment.
Excellent resistance to vertical loads and durability, high-power models (≥ 1000kW) use sliding bearings to stably withstand the vertical load of the equipment's own weight (with a maximum axial load capacity of up to 50kN). The bearing chamber contains an independent lubrication circuit, paired with an oil temperature monitoring system. This can prevent bearing wear caused by "lubricant precipitation" during vertical installation, extending the bearing life to over 20000 hours.
The cooling solution offers broad adaptability. To address the issue of heat accumulation at the bottom of vertically mounted units, standard models utilize the IC86W. This provides 40% higher cooling efficiency than conventional self-ventilated designs, meeting temperature rise requirements during high-power operation. For high-temperature environments, the IC616 forced air cooling system can be provided as a customized option. Use an external fan to dissipate heat, ensuring the motor temperature rise does not exceed the limit for Class F insulation.
3. Scope of Application
The vertical high voltage electric motor features vertical drive and heavy-duty capabilities. It is primarily designed for big equipment which require vertical installation in heavy industrial applications, including:
|
Hydropower Industry |
Drive vertical hydroelectric pumps (used for water storage/drainage in hydroelectric power plants and pump stations) and vertical hoists (used for controlling the operation of reservoir gates). Requires endurance against prolonged submerged vertical loads and outdoor environments, with compatibility for IP55 protection and air/water cooling solutions. |
|
Metallurgical Industry |
Used for the main drive of vertical rolling mills (steel plate/pipe rolling in steel mills) and vertical continuous casting machines (molten steel casting equipment). Requires stable high-torque output under high-temperature and dusty conditions to prevent "shaft breakage" or "speed drop" during rolling operations. |
|
Mining and Building Materials Industry |
Used in vertical ball mills (for grinding ore in mines and cement clinker in cement plants) and vertical hoists (for vertical ore transportation in mines). Capable of withstanding periodic impact loads during equipment operation, while its dust-proof structure minimizes failures caused by dust ingress into the motor. |
|
Power Industry |
Vertical feedwater pumps for thermal power plants (delivering high-pressure water to boilers) and vertical circulating water pumps for nuclear power plants must ensure stable operation under high-voltage grid fluctuations (±10% voltage variation). |
4.Operating environment:
Please refer to the information below for the operating environment.
Temperature Conditions Ambient temperature -15°C to 40°C (customization)
Altitude Restrictions Not exceeding 1000m; higher altitudes require prior specification;
Power Requirements 380V (customization)
Frequency 50/60Hz
Power Requirements Voltage fluctuations of ±5% and frequency fluctuations of ±2% are permitted.
Operating Conditions: Non-corrosive gas environments with no severe vibration
Foundation support at least 1.5 times the total weight of the motor
5.Model Description
Taking YL5003-4 as an example,explain the model designation of the vertical high voltage electric motor.
|
YL |
Motor Series |
|
500 |
Frame |
|
3 |
Core length designation |
|
4 |
Poles |
6.Order Instructions
Please indicate the following information when placing your order:
|
Motor model: YL5003-4 |
||
|
1 |
Rated Voltage |
6kV |
|
2 |
Rated frequency |
50Hz |
|
3 |
Rated power |
1400kw |
|
5 |
Poles |
4 |
|
6 |
Protection level |
IP55 |
|
7 |
Cooling method |
IC86W |
|
8 |
Installation type |
IMB3 |
|
9 |
Rotation direction |
Clockwise direction (viewed from the extension end of the motor shaft) |
|
10 |
Outlet box location |
at the top of the motor |
|
Note: If you have specific requirements for parameters such as frequency, voltage, ambient temperature, or altitude for Variable frequency motor, please clearly specify these when placing your order. If the required data catalog is unavailable, you may also inquire about and request a customized version. |
||
7.Catalogue
Some of the parameters are as follows:
| Type | Rated output (kW) |
Stator current (A) |
Rated speed (r/min) |
Eff. (%) |
Power factor (cos) |
Breakdown torque |
Locked- rotor torque |
Locked- rotor current |
Motors Moment of inertia | Weight(kg) | |||
| Ratedt orque |
Rated torque |
Rated current |
Motor Jm (kg ·m2) |
Permis-sible load J (kg ·m2) |
Y | YKS | YL | ||||||
| Y5004-12 | 500 | 65.4 | 495 | 93.1 | 0.79 | 1.8 | 0.8 | 5.5 | 53 | 2385 | 4700 | 5600 | 5050 |
| Y5005-12 | 560 | 73.2 | 495 | 93.2 | 0.79 | 1.8 | 0.8 | 5.5 | 56 | 2550 | 4850 | 5750 | 5200 |
| Y5601-12 | 500 | 65.4 | 495 | 93.1 | 0.79 | 1.8 | 0.7 | 6.0 | 103 | 2411 | 6160 | 7060 | 6600 |
| Y5602-12 | 560 | 73.2 | 495 | 93.2 | 0.79 | 1.8 | 0.7 | 6.0 | 114 | 2673 | 6360 | 7310 | 6860 |
| Y5603-12 | 630 | 82.2 | 495 | 93.3 | 0.79 | 1.8 | 0.7 | 6.0 | 127 | 2974 | 6570 | 7430 | 7070 |
| Y5604-12 | 710 | 92.6 | 495 | 93.4 | 0.79 | 1.8 | 0.7 | 6.0 | 139 | 3250 | 6780 | 7550 | 7280 |
For more information, please contact us as follows:


Hot Tags: vertical high voltage electric motor, China vertical high voltage electric motor manufacturers, suppliers, factory, high voltage motor for motor amplifier, high voltage motor for motor certifier, high voltage motor for motor engineering, high voltage motor for motor inductor, high voltage motor for motor sensor, high voltage motor for motor transformer